  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 401
U90 Ladder Software Manual
394
must set the M90's RS232 parameter Flow Control to N
(none).
CANbus network problems
Problem Possible cause Recommended Action
Failed
communication
Baud rate
settings
All M90's in the network must be set to the same
CANbus baud rate. These may be edited in the M90
OPLC Advanced settings.
Termination
resistors
Check the M90 user guide for details.
CANbus power
supply
Check that the CANbus power supply is properly
connected, and that the voltage is in the permissible
range as described in the M90 User Guide.
Incorrect ID
number
You may not have assigned the correct unit ID
number in your operand addresses (between 1-63).
Check in the M90 OPLC settings.
PC cannot
communicate
with bridge
Incorrect ID
number
When you communicate with the M90 unit that you
are using as a bridge to the network, select Unit ID
number 0, or select Stand-alone project in the M90
OPLC settings.
PC cannot
communicate
with network
Communication
settings
If you are trying to communicate with an M90
network via a bridge, you must define your project
as a Network project--however, U90 Ladder cannot
automatically detect communication settings in a
Network project.
Make sure the current RS232 parameters in your
project are the same as the parameters that are
actually in the bridge.
Incorrect baud
rate
The bridge's RS232 port's baud rate cannot be set
below 9600.
M90 does not turn on
When the M90 is turned on, the display screen is lit.
Note that the screen can display messages only after you download HMI displays to the
M90. If you have not downloaded displays, check the screen by pressing the 'i' button for a
few seconds to enter Information Mode. If no text appears on the screen, the M90 may not
be receiving turned on.
If your M90 does not turn on
Check that the power supply's voltage is in the permissible range in accordance to
the technical specifications for your model.
Check the M90's connections. The +24VDC must be connected to the + V terminal,
and the ground connected to the 0V terminal.
Make sure that the 24VDC output power supply is connected to a functioning AC
power source.
Check your fuses or circuit breakers. These must allow power flow.
Make certain that the power is ON.
If you have checked all of the above, and the M90 does not turn on, contact your local
distributor.