U90 Ladder Software Manual
376
modem) and the Data Terminal Equipment
(DTE; the controller or PC). The arrows
below show the direction of data flow.
Note
Unitronics’ controllers do not
support the control lines. This is
why the DTE side of the table
comprises only 3 pins.
Note Since the DSR can be
permanently set to ON,
connecting it to the RTS causes
the terminal always be ready to
transmit\receive data.
M90 modem communication problems
If your M90 is transferring data via modem, you can begin troubleshooting by entering
Information Mode. You can then check the status of relevant System Bits and Integers to
help diagnose the problem.
To begin diagnosing the problem, check the error code contained in SI 70. Refer to the
error code table in How the M90 works with a modem.
The tables below show the more common causes of modem communication problems.
Problem SI 70 value Possible Cause & Recommended Action
Modem fails to
initialize
2: Modem Did
Not Reply
M90-to-modem cable:
Make sure that the cable is securely connected.
Check the M90 modem connection and pin-out of the
M90-to-modem adapter cables. Note that if you use
cables comprising this pin-out, you must set the
RS232 parameter Flow Control to N (none).
Incompatible communication settings.
Most modems automatically match the parameters of
incoming data: baud rate, data bits, parity & stop
bits. The M90's embedded modem settings are:
9600, 8 data bits, no parity, 1 stop bit. You may
need to manually change your modem's
communication settings to match these via
Hyperterminal.
0: No Error SB 72 OFF:
In order to work with a modem, you must select 'Use
modem' in the M90 Modem Configuration box . This
causes SB 72 Initialize Modem to turn ON when the
M90 powers up.
Note that if the M90 has also been configured to use
SMS messaging, that the M90 will not be able to
connect to a modem because the SMS feature
overrides the modem.
Check too, that SB 72 is not disabled in your
program.
6: Modem Report
Error
Check the modem initialization commands. Refer to
Configuring the M90 to use a modem.
Other problems:
Problem Possible cause Recommended action
Modem is busy Modem is
engaged,
or is being
initialized
Check that the modem is free.
Use the SBs: Modem Initialization Status listed above to
check the COM port status; communications cannot flow
through the port during initialization. For more
information check the topic How the M90 works with a
modem.
Handshake Modem Check the PLC-to-modem connection and pin-out,